R22 Tools
R22 HVAC Tools & Legacy System Equipment
Professional tools and equipment for R22 (HCFC-22) refrigerant systems. Whilst R22 is being phased out globally, millions of existing HVAC systems still require service, maintenance, and refrigerant recovery with proper R22-compatible equipment.
R22 Phase-Out Status
R22 is being phased out due to its ozone depletion potential:
- EU ban: Production and import banned since 2010 (virgin R22)
- UK status: New R22 installations prohibited, existing systems can be serviced with reclaimed refrigerant
- Reclaimed R22: Available for servicing existing systems
- Recovery mandatory: All R22 must be recovered, not vented
- System lifespan: Many R22 systems still operational and require ongoing service
R22 Compatible Tools & Equipment
Manifolds & Gauges
Pressure gauges and manifold sets calibrated for R22 refrigerant:
- Pressure scales showing R22 saturation temperatures
- Standard 1/4" SAE fittings for universal compatibility
- Digital and analogue options available
- Suitable for R22 diagnostics and charging
R22 Recovery Machines
Professional recovery equipment for R22 reclamation:
- Mandatory for R22 service: Venting R22 is illegal
- High-efficiency recovery: Reclaim R22 for reuse or proper disposal
- DOT-approved cylinders: Store recovered R22 safely
- Compliance essential: Meet environmental regulations
Leak Detectors
Electronic leak detectors calibrated for HCFC refrigerants:
- Sensitive to R22 and other HCFC gases
- Essential for locating leaks before recovery
- Prevents refrigerant loss during service
- Helps identify systems requiring repair or replacement
Vacuum Pumps & Charging Equipment
Standard HVAC service equipment suitable for R22 systems:
- Vacuum pumps for system evacuation
- Refrigerant scales for accurate charging
- Charging hoses and accessories
- Service tools for R22 maintenance
Retrofit & Conversion Tools
Equipment for converting R22 systems to alternative refrigerants:
- Retrofit kits for R407C, R422D, or R438A conversion
- Flushing equipment for system cleaning
- Compatibility testing tools
- Conversion documentation and labelling
R22 System Applications
R22 is still found in many existing systems:
- Commercial air conditioning: Older office buildings and retail spaces
- Industrial refrigeration: Cold storage and process cooling
- Residential HVAC: Pre-2010 air conditioning and heat pump systems
- Chiller systems: Large commercial and industrial chillers
- Walk-in coolers: Commercial refrigeration in food service
Service Options for R22 Systems
Continue with Reclaimed R22
Service existing systems using reclaimed R22 refrigerant:
- Pros: No system modifications required, maintains original performance
- Cons: Reclaimed R22 is increasingly expensive and has limited availability
- Best for: Systems in good condition with several years of service life remaining
Retrofit to Alternative Refrigerant
Convert R22 systems to drop-in or near-drop-in alternatives:
- R407C: Most common R22 replacement (requires POE oil change)
- R422D / R438A: Drop-in alternatives (minimal modifications)
- Pros: Extends system life, more affordable refrigerant
- Cons: May require oil change, slight performance differences
System Replacement
Replace the R22 system with modern, efficient equipment:
- R410A systems: Higher efficiency, environmentally friendlier
- R32 systems: Lower GWP, excellent efficiency
- Natural refrigerants: R290 for suitable applications
- Long-term solution: Modern equipment with better performance
R22 Refrigerant Facts
- Chemical name: Chlorodifluoromethane (HCFC-22)
- ASHRAE number: R22
- GWP: 1,810 (100-year horizon)
- ODP: 0.055 (ozone depleting)
- Flammability: Non-flammable (A1 classification)
- Colour code: Green cylinder
- Phase-out reason: Ozone depletion (Montreal Protocol)
R22 vs Modern Refrigerants
| Property | R22 | R410A | R32 |
|---|---|---|---|
| ODP | 0.055 | 0 | 0 |
| GWP | 1,810 | 2,088 | 675 |
| Status | Phased out | Current (being replaced) | Modern alternative |
| Pressure | Standard | High (1.6x R22) | High (similar to R410A) |
| Efficiency | Baseline | Higher | Highest |
Legal & Compliance
- Recovery mandatory: R22 must never be vented to atmosphere
- Reclaimed only: Virgin R22 production banned in EU/UK
- Proper disposal: Recovered R22 must be reclaimed or destroyed
- Documentation: Keep records of R22 recovery and disposal
- F-Gas regulations: R22 is subject to strict handling requirements
Important Notes
- Recovery is mandatory: Never vent R22 to the atmosphere (illegal and harmful)
- Limited availability: Reclaimed R22 supply decreasing, prices increasing
- Plan for replacement: Consider system replacement or retrofit options
- Proper training: Ensure technicians are F-Gas certified for R22 handling
Need help with R22 service equipment or retrofit options? Contact our technical team for expert advice on R22 recovery, system maintenance, and conversion solutions.